Why does my electric oven present the option of 40A and 50A breakers?Why does the main circuit breaker trip but not the smaller branch circuit breakers?What amp breaker for 20 Amp electrical oven and 40 Amp electrical range on same circuitDoes an wall-mounted electric oven require an air gap below, and if so, how large?Maximum breaker on NMD7 8/3 wire?Three wire supply and Four Prong Oven?Can I use 6-2 NM W/G when running a new 50A branch circuit to my cooktop?Electric oven: Bake and Broil not WorkingGas Range requires 120V 15A yet comes with a Nema 14-50 PlugConverting KFDD500ESS Dual Fuel Range from 4 wire to 3 wire plugWho can I ask to install a 30 amp rated range on a 30 amp circuit (not as easy as it sounds)

Future enhancements for the finite element method

Rotated Position of Integers

Why is Colorado so different politically from nearby states?

How should I push back against my job assigning "homework"?

Does a component pouch automatically contain components?

Beginner's snake game using PyGame

Looking after a wayward brother in mother's will

arcpy.GetParameterAsText not passing arguments to script?

If Sweden was to magically float away, at what altitude would it be visible from the southern hemisphere?

Could IPv6 make NAT / port numbers redundant?

Accidentally cashed a check twice

Order by does not work as I expect

Scala list with same adjacent values

Asking bank to reduce APR instead of increasing credit limit

How can I offer a test ride while selling a bike?

Is American Express widely accepted in France?

How can an eldritch abomination hide its true form in public?

Orientable with respect to complex cobordism?

Where can I find the list of all tendons in the human body?

What is the most important characteristic of New Weird as a genre?

Double integral bounds of integration polar change of coordinate

Is there a rule that prohibits us from using 2 possessives in a row?

What caused the tendency for conservatives to not support climate change regulations?

Term for checking piece whose opponent daren't capture it



Why does my electric oven present the option of 40A and 50A breakers?


Why does the main circuit breaker trip but not the smaller branch circuit breakers?What amp breaker for 20 Amp electrical oven and 40 Amp electrical range on same circuitDoes an wall-mounted electric oven require an air gap below, and if so, how large?Maximum breaker on NMD7 8/3 wire?Three wire supply and Four Prong Oven?Can I use 6-2 NM W/G when running a new 50A branch circuit to my cooktop?Electric oven: Bake and Broil not WorkingGas Range requires 120V 15A yet comes with a Nema 14-50 PlugConverting KFDD500ESS Dual Fuel Range from 4 wire to 3 wire plugWho can I ask to install a 30 amp rated range on a 30 amp circuit (not as easy as it sounds)






.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








2















The oven in question states 40A with 120/240 volts.



In the installation manual:




This range is manufactured with the neutral terminal connected to the
cabinet. Use a 3-wire, UL Listed. 40- or 50-amp power supply cord
(pigtail) (see following Range Rating chart). If local codes do not
permit ground through the neutral, use a 4-wire power supply cord
rated at 250 volts, 40 or 50 amps and investigated for use with
ranges.




To me this is saying a minimum of 40A cable but can use 50A.



If I install a 40A then how much safety buffer is included? Is there a safety factor built into the stated slide in oven 40A rating? ie it will only pull up to a certain % below the 40A rating? I do not imagine running a 40A cable where during operation its reaching the upper limit of the cable and associated breaker.



Also why state: 120/240 volts?



How do i decipher the meaning of 120/240 volts isnt it one or the other??










share|improve this question
























  • You seem to be asking about the engineering decisions made by the manufacturer. That's a bit outside the scope of DIY home improvement. Why the concern? They wouldn't have specced a 40A circuit if it was a safety or nuisance trip issue.

    – isherwood
    9 hours ago












  • Want to know the why behind it.

    – Andrew Bannerman
    9 hours ago

















2















The oven in question states 40A with 120/240 volts.



In the installation manual:




This range is manufactured with the neutral terminal connected to the
cabinet. Use a 3-wire, UL Listed. 40- or 50-amp power supply cord
(pigtail) (see following Range Rating chart). If local codes do not
permit ground through the neutral, use a 4-wire power supply cord
rated at 250 volts, 40 or 50 amps and investigated for use with
ranges.




To me this is saying a minimum of 40A cable but can use 50A.



If I install a 40A then how much safety buffer is included? Is there a safety factor built into the stated slide in oven 40A rating? ie it will only pull up to a certain % below the 40A rating? I do not imagine running a 40A cable where during operation its reaching the upper limit of the cable and associated breaker.



Also why state: 120/240 volts?



How do i decipher the meaning of 120/240 volts isnt it one or the other??










share|improve this question
























  • You seem to be asking about the engineering decisions made by the manufacturer. That's a bit outside the scope of DIY home improvement. Why the concern? They wouldn't have specced a 40A circuit if it was a safety or nuisance trip issue.

    – isherwood
    9 hours ago












  • Want to know the why behind it.

    – Andrew Bannerman
    9 hours ago













2












2








2








The oven in question states 40A with 120/240 volts.



In the installation manual:




This range is manufactured with the neutral terminal connected to the
cabinet. Use a 3-wire, UL Listed. 40- or 50-amp power supply cord
(pigtail) (see following Range Rating chart). If local codes do not
permit ground through the neutral, use a 4-wire power supply cord
rated at 250 volts, 40 or 50 amps and investigated for use with
ranges.




To me this is saying a minimum of 40A cable but can use 50A.



If I install a 40A then how much safety buffer is included? Is there a safety factor built into the stated slide in oven 40A rating? ie it will only pull up to a certain % below the 40A rating? I do not imagine running a 40A cable where during operation its reaching the upper limit of the cable and associated breaker.



Also why state: 120/240 volts?



How do i decipher the meaning of 120/240 volts isnt it one or the other??










share|improve this question
















The oven in question states 40A with 120/240 volts.



In the installation manual:




This range is manufactured with the neutral terminal connected to the
cabinet. Use a 3-wire, UL Listed. 40- or 50-amp power supply cord
(pigtail) (see following Range Rating chart). If local codes do not
permit ground through the neutral, use a 4-wire power supply cord
rated at 250 volts, 40 or 50 amps and investigated for use with
ranges.




To me this is saying a minimum of 40A cable but can use 50A.



If I install a 40A then how much safety buffer is included? Is there a safety factor built into the stated slide in oven 40A rating? ie it will only pull up to a certain % below the 40A rating? I do not imagine running a 40A cable where during operation its reaching the upper limit of the cable and associated breaker.



Also why state: 120/240 volts?



How do i decipher the meaning of 120/240 volts isnt it one or the other??







electrical






share|improve this question















share|improve this question













share|improve this question




share|improve this question








edited 9 hours ago









isherwood

52.6k562137




52.6k562137










asked 9 hours ago









Andrew BannermanAndrew Bannerman

1153




1153












  • You seem to be asking about the engineering decisions made by the manufacturer. That's a bit outside the scope of DIY home improvement. Why the concern? They wouldn't have specced a 40A circuit if it was a safety or nuisance trip issue.

    – isherwood
    9 hours ago












  • Want to know the why behind it.

    – Andrew Bannerman
    9 hours ago

















  • You seem to be asking about the engineering decisions made by the manufacturer. That's a bit outside the scope of DIY home improvement. Why the concern? They wouldn't have specced a 40A circuit if it was a safety or nuisance trip issue.

    – isherwood
    9 hours ago












  • Want to know the why behind it.

    – Andrew Bannerman
    9 hours ago
















You seem to be asking about the engineering decisions made by the manufacturer. That's a bit outside the scope of DIY home improvement. Why the concern? They wouldn't have specced a 40A circuit if it was a safety or nuisance trip issue.

– isherwood
9 hours ago






You seem to be asking about the engineering decisions made by the manufacturer. That's a bit outside the scope of DIY home improvement. Why the concern? They wouldn't have specced a 40A circuit if it was a safety or nuisance trip issue.

– isherwood
9 hours ago














Want to know the why behind it.

– Andrew Bannerman
9 hours ago





Want to know the why behind it.

– Andrew Bannerman
9 hours ago










4 Answers
4






active

oldest

votes


















2














There are a few different issues here:



  • 120 vs. 240

A typical oven for installation in a system like the US (split 120/240) will use 240V for the heating elements (i.e., needs 2 hot wires) and 120V for the controls (i.e., needs 1 hot, 1 neutral). So you can't run it on only 120 or only 240. That is different from, for example, a computer power supply that might list 120 - 240 (or more typically something like 100 - 250) which means that any voltage in that range is OK. That is because a computer uses a power supply that can take "anything" and convert to a single lower voltage. An oven will actually use the power "as is" (at least for heating elements and lights) and has to get what it needs or it won't work properly.



  • 40A/50A

An oven is designed with specific power requirements. It will not, unless damaged, exceed those requirements. In addition, as a device with a continuous load (i.e., it can be on for a while), it will actually be designed to use less (I think the normal number is <= 80% of the rated current) power. So there is plenty of safety margin even at 40A, by design. As far as 50A, there are some ovens that require 50A instead of 40A. By designing a 40A oven so that it can operate safely on a 50A circuit - i.e., that it is engineered such that the breaker not tripping until 50A instead of 40A is "OK", that gives a little bit of flexibility on the installation. Otherwise, if you had a 50A circuit (both appropriate wire and a 50A breaker), you would need to replace the 50A breaker with a 40A breaker in order to install this oven - but that is not the case here and you are fine with 40A or 50A.



  • ground through the neutral

You didn't ask about this part, but I will tell you anyway. For historical reasons, many ovens used to have no ground and then later ground was piggybacked on the neutral wire. That is not safe (though marginally better than no ground at all) and is not recommended, even if local code permits it. If you have a hardwired oven then you need to connect the oven ground to either a ground wire or (if you have a metal junction box attached to metal conduit going all the way back to the breaker panel) to a metal box. If you have a plug-in installation then you need to use a properly wired 4-wire socket (NEMA 14-50) connected to 2 hots, 1 neutral and 1 ground (ground again can be metal box/conduit). If you have an older 3-wire socket, now is the time to replace it - and yes that may require running a new cable.






share|improve this answer


















  • 1





    Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

    – Andrew Bannerman
    8 hours ago












  • Perfect. Voltage drop should not be an issue at all with 50'.

    – manassehkatz
    8 hours ago






  • 1





    Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

    – JPhi1618
    8 hours ago












  • GE 40 Amp Double Pole Bolt-On Breaker.

    – Andrew Bannerman
    8 hours ago







  • 1





    @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

    – JPhi1618
    8 hours ago


















4














3-prong vs 4-prong



3-prong connections lack ground; they bootleg ground off neutral and if neutral breaks, it guarantees the appliance is electrified.



Appliance manufactures are terrified of losing sales (or much worse, getting customer returns!) because the installed power was not right for their appliance. That's why they lobbied to allow new 3-wire bootlegs so late (1989 they were finally outlawed?) and to have old 3-wire connections stay grandfathered. Hence shipping it with a 3-wire, and the sneaky language encouraging 3-wire even though that's usually illegal and certainly unsafe.*



If your wall box doesn't have separate neutral and ground, then either retrofit a #10 ground wire (allowed now), or put a GFCI breaker on it and label the socket "GFCI Protected/No Equipment Ground".



40A vs 50A



Common kitchen range circuits are either 40A or 50A.



If it's wired with #8 cable, it must be breakered for 40A. If it is wired with #6 cable, it can be breakered 50A - though a 40A breaker is also allowed. (that would be a case of using larger wire than is required; that's always allowed).



Either way, they use a 50A receptacle because 40A receptacles do not exist.



This manufacturer chose to pay a little extra to Underwriter's Laboratories (UL) to certify their oven both for a 40A supply and for a 50A supply. So the customer can just "drop it in" to either situation. It's back to avoiding lost sales.



That is legal because UL says it is legal, because it passed UL's battery of tests and design requirements. Given the narrow ampacity range, that's not a high bar.




* what they fail to mention is it's required in most cases. You're not allowed to downgrade a 4-wire connection to 3-wire (the sneaky instructions sure sound like they're suggesting that, eh?) -- So if the house was built 4-wire (certainly any after the 1989? NEC came to force)... or was previously upgraded for 4-wire, you can't downgrade it now. Metal conduit installations, conduit is the ground. "Local codes" (read: they adopted NEC) do not permit 3-wire in any of those cases, and that's effectively national. Add to it localities who put their foot down and said "ENOUGH!"



In short, if neutral and ground are separate in your box, you must use 4-wire.






share|improve this answer

























  • Thanks for this explanation. Great post replies and have a more complete picture! Thanks

    – Andrew Bannerman
    6 hours ago






  • 1





    Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

    – Mazura
    27 mins ago


















3














The reason they give the option of 40A or 50A is because 50A is a standard circuit size a builder would install for a wall oven or range. However, they also want you to know that if you are running wire specifically for this oven, 40A would suffice. For the sake of future upgrades, you should stick with 50A. You want to choose the most common "standard" size for appliances whenever possible.



As far as the 240/120v specification - this is because the appliance requires a neutral. It will have 3 wires - red, black and white. The voltage from red to black is 240v, and the voltage between red and white and black and white will be 120v. This allows the appliance to use 240v for the heating coils, but can run the electronics or fans with 120v. This is common on ranges and ovens, but something like a water heater has no electronics other than the heating coils so they only need two wires (red and black, typically) for 240v. In modern construction every circuit would also have a ground wire but older homes may not have that for large appliances.






share|improve this answer






























    1














    I'm not sure what your specific concern is, but here are a few points that may lend clarity:



    • The manufacturer states that a 40A circuit is adequate. Take them at their word that you won't have safety or nuisance trip problem.

    • They're offering the option of using a 50A circuit because the circuit protects the wiring leading to the device, not the device itself, and you may want the option to upgrade appliances later.

    • There is some degree of protection for the device in not drastically oversizing the circuit, but the device has integral safety mechanisms for current and thermal overload.

    • Again, the breaker protects the wiring, so be sure that the wire size you use is up to the task of whatever the breaker will allow. Do not use #8 wire on a 50A breaker, for example.





    share|improve this answer























      Your Answer








      StackExchange.ready(function()
      var channelOptions =
      tags: "".split(" "),
      id: "73"
      ;
      initTagRenderer("".split(" "), "".split(" "), channelOptions);

      StackExchange.using("externalEditor", function()
      // Have to fire editor after snippets, if snippets enabled
      if (StackExchange.settings.snippets.snippetsEnabled)
      StackExchange.using("snippets", function()
      createEditor();
      );

      else
      createEditor();

      );

      function createEditor()
      StackExchange.prepareEditor(
      heartbeatType: 'answer',
      autoActivateHeartbeat: false,
      convertImagesToLinks: false,
      noModals: true,
      showLowRepImageUploadWarning: true,
      reputationToPostImages: null,
      bindNavPrevention: true,
      postfix: "",
      imageUploader:
      brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
      contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
      allowUrls: true
      ,
      noCode: true, onDemand: true,
      discardSelector: ".discard-answer"
      ,immediatelyShowMarkdownHelp:true
      );



      );













      draft saved

      draft discarded


















      StackExchange.ready(
      function ()
      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f166152%2fwhy-does-my-electric-oven-present-the-option-of-40a-and-50a-breakers%23new-answer', 'question_page');

      );

      Post as a guest















      Required, but never shown

























      4 Answers
      4






      active

      oldest

      votes








      4 Answers
      4






      active

      oldest

      votes









      active

      oldest

      votes






      active

      oldest

      votes









      2














      There are a few different issues here:



      • 120 vs. 240

      A typical oven for installation in a system like the US (split 120/240) will use 240V for the heating elements (i.e., needs 2 hot wires) and 120V for the controls (i.e., needs 1 hot, 1 neutral). So you can't run it on only 120 or only 240. That is different from, for example, a computer power supply that might list 120 - 240 (or more typically something like 100 - 250) which means that any voltage in that range is OK. That is because a computer uses a power supply that can take "anything" and convert to a single lower voltage. An oven will actually use the power "as is" (at least for heating elements and lights) and has to get what it needs or it won't work properly.



      • 40A/50A

      An oven is designed with specific power requirements. It will not, unless damaged, exceed those requirements. In addition, as a device with a continuous load (i.e., it can be on for a while), it will actually be designed to use less (I think the normal number is <= 80% of the rated current) power. So there is plenty of safety margin even at 40A, by design. As far as 50A, there are some ovens that require 50A instead of 40A. By designing a 40A oven so that it can operate safely on a 50A circuit - i.e., that it is engineered such that the breaker not tripping until 50A instead of 40A is "OK", that gives a little bit of flexibility on the installation. Otherwise, if you had a 50A circuit (both appropriate wire and a 50A breaker), you would need to replace the 50A breaker with a 40A breaker in order to install this oven - but that is not the case here and you are fine with 40A or 50A.



      • ground through the neutral

      You didn't ask about this part, but I will tell you anyway. For historical reasons, many ovens used to have no ground and then later ground was piggybacked on the neutral wire. That is not safe (though marginally better than no ground at all) and is not recommended, even if local code permits it. If you have a hardwired oven then you need to connect the oven ground to either a ground wire or (if you have a metal junction box attached to metal conduit going all the way back to the breaker panel) to a metal box. If you have a plug-in installation then you need to use a properly wired 4-wire socket (NEMA 14-50) connected to 2 hots, 1 neutral and 1 ground (ground again can be metal box/conduit). If you have an older 3-wire socket, now is the time to replace it - and yes that may require running a new cable.






      share|improve this answer


















      • 1





        Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

        – Andrew Bannerman
        8 hours ago












      • Perfect. Voltage drop should not be an issue at all with 50'.

        – manassehkatz
        8 hours ago






      • 1





        Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

        – JPhi1618
        8 hours ago












      • GE 40 Amp Double Pole Bolt-On Breaker.

        – Andrew Bannerman
        8 hours ago







      • 1





        @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

        – JPhi1618
        8 hours ago















      2














      There are a few different issues here:



      • 120 vs. 240

      A typical oven for installation in a system like the US (split 120/240) will use 240V for the heating elements (i.e., needs 2 hot wires) and 120V for the controls (i.e., needs 1 hot, 1 neutral). So you can't run it on only 120 or only 240. That is different from, for example, a computer power supply that might list 120 - 240 (or more typically something like 100 - 250) which means that any voltage in that range is OK. That is because a computer uses a power supply that can take "anything" and convert to a single lower voltage. An oven will actually use the power "as is" (at least for heating elements and lights) and has to get what it needs or it won't work properly.



      • 40A/50A

      An oven is designed with specific power requirements. It will not, unless damaged, exceed those requirements. In addition, as a device with a continuous load (i.e., it can be on for a while), it will actually be designed to use less (I think the normal number is <= 80% of the rated current) power. So there is plenty of safety margin even at 40A, by design. As far as 50A, there are some ovens that require 50A instead of 40A. By designing a 40A oven so that it can operate safely on a 50A circuit - i.e., that it is engineered such that the breaker not tripping until 50A instead of 40A is "OK", that gives a little bit of flexibility on the installation. Otherwise, if you had a 50A circuit (both appropriate wire and a 50A breaker), you would need to replace the 50A breaker with a 40A breaker in order to install this oven - but that is not the case here and you are fine with 40A or 50A.



      • ground through the neutral

      You didn't ask about this part, but I will tell you anyway. For historical reasons, many ovens used to have no ground and then later ground was piggybacked on the neutral wire. That is not safe (though marginally better than no ground at all) and is not recommended, even if local code permits it. If you have a hardwired oven then you need to connect the oven ground to either a ground wire or (if you have a metal junction box attached to metal conduit going all the way back to the breaker panel) to a metal box. If you have a plug-in installation then you need to use a properly wired 4-wire socket (NEMA 14-50) connected to 2 hots, 1 neutral and 1 ground (ground again can be metal box/conduit). If you have an older 3-wire socket, now is the time to replace it - and yes that may require running a new cable.






      share|improve this answer


















      • 1





        Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

        – Andrew Bannerman
        8 hours ago












      • Perfect. Voltage drop should not be an issue at all with 50'.

        – manassehkatz
        8 hours ago






      • 1





        Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

        – JPhi1618
        8 hours ago












      • GE 40 Amp Double Pole Bolt-On Breaker.

        – Andrew Bannerman
        8 hours ago







      • 1





        @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

        – JPhi1618
        8 hours ago













      2












      2








      2







      There are a few different issues here:



      • 120 vs. 240

      A typical oven for installation in a system like the US (split 120/240) will use 240V for the heating elements (i.e., needs 2 hot wires) and 120V for the controls (i.e., needs 1 hot, 1 neutral). So you can't run it on only 120 or only 240. That is different from, for example, a computer power supply that might list 120 - 240 (or more typically something like 100 - 250) which means that any voltage in that range is OK. That is because a computer uses a power supply that can take "anything" and convert to a single lower voltage. An oven will actually use the power "as is" (at least for heating elements and lights) and has to get what it needs or it won't work properly.



      • 40A/50A

      An oven is designed with specific power requirements. It will not, unless damaged, exceed those requirements. In addition, as a device with a continuous load (i.e., it can be on for a while), it will actually be designed to use less (I think the normal number is <= 80% of the rated current) power. So there is plenty of safety margin even at 40A, by design. As far as 50A, there are some ovens that require 50A instead of 40A. By designing a 40A oven so that it can operate safely on a 50A circuit - i.e., that it is engineered such that the breaker not tripping until 50A instead of 40A is "OK", that gives a little bit of flexibility on the installation. Otherwise, if you had a 50A circuit (both appropriate wire and a 50A breaker), you would need to replace the 50A breaker with a 40A breaker in order to install this oven - but that is not the case here and you are fine with 40A or 50A.



      • ground through the neutral

      You didn't ask about this part, but I will tell you anyway. For historical reasons, many ovens used to have no ground and then later ground was piggybacked on the neutral wire. That is not safe (though marginally better than no ground at all) and is not recommended, even if local code permits it. If you have a hardwired oven then you need to connect the oven ground to either a ground wire or (if you have a metal junction box attached to metal conduit going all the way back to the breaker panel) to a metal box. If you have a plug-in installation then you need to use a properly wired 4-wire socket (NEMA 14-50) connected to 2 hots, 1 neutral and 1 ground (ground again can be metal box/conduit). If you have an older 3-wire socket, now is the time to replace it - and yes that may require running a new cable.






      share|improve this answer













      There are a few different issues here:



      • 120 vs. 240

      A typical oven for installation in a system like the US (split 120/240) will use 240V for the heating elements (i.e., needs 2 hot wires) and 120V for the controls (i.e., needs 1 hot, 1 neutral). So you can't run it on only 120 or only 240. That is different from, for example, a computer power supply that might list 120 - 240 (or more typically something like 100 - 250) which means that any voltage in that range is OK. That is because a computer uses a power supply that can take "anything" and convert to a single lower voltage. An oven will actually use the power "as is" (at least for heating elements and lights) and has to get what it needs or it won't work properly.



      • 40A/50A

      An oven is designed with specific power requirements. It will not, unless damaged, exceed those requirements. In addition, as a device with a continuous load (i.e., it can be on for a while), it will actually be designed to use less (I think the normal number is <= 80% of the rated current) power. So there is plenty of safety margin even at 40A, by design. As far as 50A, there are some ovens that require 50A instead of 40A. By designing a 40A oven so that it can operate safely on a 50A circuit - i.e., that it is engineered such that the breaker not tripping until 50A instead of 40A is "OK", that gives a little bit of flexibility on the installation. Otherwise, if you had a 50A circuit (both appropriate wire and a 50A breaker), you would need to replace the 50A breaker with a 40A breaker in order to install this oven - but that is not the case here and you are fine with 40A or 50A.



      • ground through the neutral

      You didn't ask about this part, but I will tell you anyway. For historical reasons, many ovens used to have no ground and then later ground was piggybacked on the neutral wire. That is not safe (though marginally better than no ground at all) and is not recommended, even if local code permits it. If you have a hardwired oven then you need to connect the oven ground to either a ground wire or (if you have a metal junction box attached to metal conduit going all the way back to the breaker panel) to a metal box. If you have a plug-in installation then you need to use a properly wired 4-wire socket (NEMA 14-50) connected to 2 hots, 1 neutral and 1 ground (ground again can be metal box/conduit). If you have an older 3-wire socket, now is the time to replace it - and yes that may require running a new cable.







      share|improve this answer












      share|improve this answer



      share|improve this answer










      answered 9 hours ago









      manassehkatzmanassehkatz

      12.8k11844




      12.8k11844







      • 1





        Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

        – Andrew Bannerman
        8 hours ago












      • Perfect. Voltage drop should not be an issue at all with 50'.

        – manassehkatz
        8 hours ago






      • 1





        Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

        – JPhi1618
        8 hours ago












      • GE 40 Amp Double Pole Bolt-On Breaker.

        – Andrew Bannerman
        8 hours ago







      • 1





        @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

        – JPhi1618
        8 hours ago












      • 1





        Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

        – Andrew Bannerman
        8 hours ago












      • Perfect. Voltage drop should not be an issue at all with 50'.

        – manassehkatz
        8 hours ago






      • 1





        Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

        – JPhi1618
        8 hours ago












      • GE 40 Amp Double Pole Bolt-On Breaker.

        – Andrew Bannerman
        8 hours ago







      • 1





        @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

        – JPhi1618
        8 hours ago







      1




      1





      Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

      – Andrew Bannerman
      8 hours ago






      Ok thanks for touching on the last point. I will be running new wire for this so: The wire will be 8/3 (red,black, neutral + ground) and in the breaker... I will have 2x 40 amp breakers (GE to match the box manufacturer), 1x for the red (hot) and 1x for the black (hot) (next to each other in the braker box), neutral to the neutral bar and ground to the ground bar - this will then be a 4x prong NEMA 14-50 plug. As far as power drop.... running 50' is power drop a concern - running this calculations (online calculator) its within the 3% tolerance.

      – Andrew Bannerman
      8 hours ago














      Perfect. Voltage drop should not be an issue at all with 50'.

      – manassehkatz
      8 hours ago





      Perfect. Voltage drop should not be an issue at all with 50'.

      – manassehkatz
      8 hours ago




      1




      1





      Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

      – JPhi1618
      8 hours ago






      Wait, you're not going to have two breakers. You're going to have one two-pole breaker, @AndrewBannerman

      – JPhi1618
      8 hours ago














      GE 40 Amp Double Pole Bolt-On Breaker.

      – Andrew Bannerman
      8 hours ago






      GE 40 Amp Double Pole Bolt-On Breaker.

      – Andrew Bannerman
      8 hours ago





      1




      1





      @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

      – JPhi1618
      8 hours ago





      @AndrewBannerman why not run a 50A circuit tho? This is a lot of work to just go with the minimum required.

      – JPhi1618
      8 hours ago













      4














      3-prong vs 4-prong



      3-prong connections lack ground; they bootleg ground off neutral and if neutral breaks, it guarantees the appliance is electrified.



      Appliance manufactures are terrified of losing sales (or much worse, getting customer returns!) because the installed power was not right for their appliance. That's why they lobbied to allow new 3-wire bootlegs so late (1989 they were finally outlawed?) and to have old 3-wire connections stay grandfathered. Hence shipping it with a 3-wire, and the sneaky language encouraging 3-wire even though that's usually illegal and certainly unsafe.*



      If your wall box doesn't have separate neutral and ground, then either retrofit a #10 ground wire (allowed now), or put a GFCI breaker on it and label the socket "GFCI Protected/No Equipment Ground".



      40A vs 50A



      Common kitchen range circuits are either 40A or 50A.



      If it's wired with #8 cable, it must be breakered for 40A. If it is wired with #6 cable, it can be breakered 50A - though a 40A breaker is also allowed. (that would be a case of using larger wire than is required; that's always allowed).



      Either way, they use a 50A receptacle because 40A receptacles do not exist.



      This manufacturer chose to pay a little extra to Underwriter's Laboratories (UL) to certify their oven both for a 40A supply and for a 50A supply. So the customer can just "drop it in" to either situation. It's back to avoiding lost sales.



      That is legal because UL says it is legal, because it passed UL's battery of tests and design requirements. Given the narrow ampacity range, that's not a high bar.




      * what they fail to mention is it's required in most cases. You're not allowed to downgrade a 4-wire connection to 3-wire (the sneaky instructions sure sound like they're suggesting that, eh?) -- So if the house was built 4-wire (certainly any after the 1989? NEC came to force)... or was previously upgraded for 4-wire, you can't downgrade it now. Metal conduit installations, conduit is the ground. "Local codes" (read: they adopted NEC) do not permit 3-wire in any of those cases, and that's effectively national. Add to it localities who put their foot down and said "ENOUGH!"



      In short, if neutral and ground are separate in your box, you must use 4-wire.






      share|improve this answer

























      • Thanks for this explanation. Great post replies and have a more complete picture! Thanks

        – Andrew Bannerman
        6 hours ago






      • 1





        Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

        – Mazura
        27 mins ago















      4














      3-prong vs 4-prong



      3-prong connections lack ground; they bootleg ground off neutral and if neutral breaks, it guarantees the appliance is electrified.



      Appliance manufactures are terrified of losing sales (or much worse, getting customer returns!) because the installed power was not right for their appliance. That's why they lobbied to allow new 3-wire bootlegs so late (1989 they were finally outlawed?) and to have old 3-wire connections stay grandfathered. Hence shipping it with a 3-wire, and the sneaky language encouraging 3-wire even though that's usually illegal and certainly unsafe.*



      If your wall box doesn't have separate neutral and ground, then either retrofit a #10 ground wire (allowed now), or put a GFCI breaker on it and label the socket "GFCI Protected/No Equipment Ground".



      40A vs 50A



      Common kitchen range circuits are either 40A or 50A.



      If it's wired with #8 cable, it must be breakered for 40A. If it is wired with #6 cable, it can be breakered 50A - though a 40A breaker is also allowed. (that would be a case of using larger wire than is required; that's always allowed).



      Either way, they use a 50A receptacle because 40A receptacles do not exist.



      This manufacturer chose to pay a little extra to Underwriter's Laboratories (UL) to certify their oven both for a 40A supply and for a 50A supply. So the customer can just "drop it in" to either situation. It's back to avoiding lost sales.



      That is legal because UL says it is legal, because it passed UL's battery of tests and design requirements. Given the narrow ampacity range, that's not a high bar.




      * what they fail to mention is it's required in most cases. You're not allowed to downgrade a 4-wire connection to 3-wire (the sneaky instructions sure sound like they're suggesting that, eh?) -- So if the house was built 4-wire (certainly any after the 1989? NEC came to force)... or was previously upgraded for 4-wire, you can't downgrade it now. Metal conduit installations, conduit is the ground. "Local codes" (read: they adopted NEC) do not permit 3-wire in any of those cases, and that's effectively national. Add to it localities who put their foot down and said "ENOUGH!"



      In short, if neutral and ground are separate in your box, you must use 4-wire.






      share|improve this answer

























      • Thanks for this explanation. Great post replies and have a more complete picture! Thanks

        – Andrew Bannerman
        6 hours ago






      • 1





        Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

        – Mazura
        27 mins ago













      4












      4








      4







      3-prong vs 4-prong



      3-prong connections lack ground; they bootleg ground off neutral and if neutral breaks, it guarantees the appliance is electrified.



      Appliance manufactures are terrified of losing sales (or much worse, getting customer returns!) because the installed power was not right for their appliance. That's why they lobbied to allow new 3-wire bootlegs so late (1989 they were finally outlawed?) and to have old 3-wire connections stay grandfathered. Hence shipping it with a 3-wire, and the sneaky language encouraging 3-wire even though that's usually illegal and certainly unsafe.*



      If your wall box doesn't have separate neutral and ground, then either retrofit a #10 ground wire (allowed now), or put a GFCI breaker on it and label the socket "GFCI Protected/No Equipment Ground".



      40A vs 50A



      Common kitchen range circuits are either 40A or 50A.



      If it's wired with #8 cable, it must be breakered for 40A. If it is wired with #6 cable, it can be breakered 50A - though a 40A breaker is also allowed. (that would be a case of using larger wire than is required; that's always allowed).



      Either way, they use a 50A receptacle because 40A receptacles do not exist.



      This manufacturer chose to pay a little extra to Underwriter's Laboratories (UL) to certify their oven both for a 40A supply and for a 50A supply. So the customer can just "drop it in" to either situation. It's back to avoiding lost sales.



      That is legal because UL says it is legal, because it passed UL's battery of tests and design requirements. Given the narrow ampacity range, that's not a high bar.




      * what they fail to mention is it's required in most cases. You're not allowed to downgrade a 4-wire connection to 3-wire (the sneaky instructions sure sound like they're suggesting that, eh?) -- So if the house was built 4-wire (certainly any after the 1989? NEC came to force)... or was previously upgraded for 4-wire, you can't downgrade it now. Metal conduit installations, conduit is the ground. "Local codes" (read: they adopted NEC) do not permit 3-wire in any of those cases, and that's effectively national. Add to it localities who put their foot down and said "ENOUGH!"



      In short, if neutral and ground are separate in your box, you must use 4-wire.






      share|improve this answer















      3-prong vs 4-prong



      3-prong connections lack ground; they bootleg ground off neutral and if neutral breaks, it guarantees the appliance is electrified.



      Appliance manufactures are terrified of losing sales (or much worse, getting customer returns!) because the installed power was not right for their appliance. That's why they lobbied to allow new 3-wire bootlegs so late (1989 they were finally outlawed?) and to have old 3-wire connections stay grandfathered. Hence shipping it with a 3-wire, and the sneaky language encouraging 3-wire even though that's usually illegal and certainly unsafe.*



      If your wall box doesn't have separate neutral and ground, then either retrofit a #10 ground wire (allowed now), or put a GFCI breaker on it and label the socket "GFCI Protected/No Equipment Ground".



      40A vs 50A



      Common kitchen range circuits are either 40A or 50A.



      If it's wired with #8 cable, it must be breakered for 40A. If it is wired with #6 cable, it can be breakered 50A - though a 40A breaker is also allowed. (that would be a case of using larger wire than is required; that's always allowed).



      Either way, they use a 50A receptacle because 40A receptacles do not exist.



      This manufacturer chose to pay a little extra to Underwriter's Laboratories (UL) to certify their oven both for a 40A supply and for a 50A supply. So the customer can just "drop it in" to either situation. It's back to avoiding lost sales.



      That is legal because UL says it is legal, because it passed UL's battery of tests and design requirements. Given the narrow ampacity range, that's not a high bar.




      * what they fail to mention is it's required in most cases. You're not allowed to downgrade a 4-wire connection to 3-wire (the sneaky instructions sure sound like they're suggesting that, eh?) -- So if the house was built 4-wire (certainly any after the 1989? NEC came to force)... or was previously upgraded for 4-wire, you can't downgrade it now. Metal conduit installations, conduit is the ground. "Local codes" (read: they adopted NEC) do not permit 3-wire in any of those cases, and that's effectively national. Add to it localities who put their foot down and said "ENOUGH!"



      In short, if neutral and ground are separate in your box, you must use 4-wire.







      share|improve this answer














      share|improve this answer



      share|improve this answer








      edited 6 hours ago

























      answered 6 hours ago









      HarperHarper

      80.5k555162




      80.5k555162












      • Thanks for this explanation. Great post replies and have a more complete picture! Thanks

        – Andrew Bannerman
        6 hours ago






      • 1





        Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

        – Mazura
        27 mins ago

















      • Thanks for this explanation. Great post replies and have a more complete picture! Thanks

        – Andrew Bannerman
        6 hours ago






      • 1





        Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

        – Mazura
        27 mins ago
















      Thanks for this explanation. Great post replies and have a more complete picture! Thanks

      – Andrew Bannerman
      6 hours ago





      Thanks for this explanation. Great post replies and have a more complete picture! Thanks

      – Andrew Bannerman
      6 hours ago




      1




      1





      Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

      – Mazura
      27 mins ago





      Only answer here that talks about wire size (that's the decisive factor on breaker ampacity, which I would've had to look up), +1. MOP (maximum over-current protection) for devices comes after that and cannot exceed the ampacity of the breaker required to protect a given size wire.

      – Mazura
      27 mins ago











      3














      The reason they give the option of 40A or 50A is because 50A is a standard circuit size a builder would install for a wall oven or range. However, they also want you to know that if you are running wire specifically for this oven, 40A would suffice. For the sake of future upgrades, you should stick with 50A. You want to choose the most common "standard" size for appliances whenever possible.



      As far as the 240/120v specification - this is because the appliance requires a neutral. It will have 3 wires - red, black and white. The voltage from red to black is 240v, and the voltage between red and white and black and white will be 120v. This allows the appliance to use 240v for the heating coils, but can run the electronics or fans with 120v. This is common on ranges and ovens, but something like a water heater has no electronics other than the heating coils so they only need two wires (red and black, typically) for 240v. In modern construction every circuit would also have a ground wire but older homes may not have that for large appliances.






      share|improve this answer



























        3














        The reason they give the option of 40A or 50A is because 50A is a standard circuit size a builder would install for a wall oven or range. However, they also want you to know that if you are running wire specifically for this oven, 40A would suffice. For the sake of future upgrades, you should stick with 50A. You want to choose the most common "standard" size for appliances whenever possible.



        As far as the 240/120v specification - this is because the appliance requires a neutral. It will have 3 wires - red, black and white. The voltage from red to black is 240v, and the voltage between red and white and black and white will be 120v. This allows the appliance to use 240v for the heating coils, but can run the electronics or fans with 120v. This is common on ranges and ovens, but something like a water heater has no electronics other than the heating coils so they only need two wires (red and black, typically) for 240v. In modern construction every circuit would also have a ground wire but older homes may not have that for large appliances.






        share|improve this answer

























          3












          3








          3







          The reason they give the option of 40A or 50A is because 50A is a standard circuit size a builder would install for a wall oven or range. However, they also want you to know that if you are running wire specifically for this oven, 40A would suffice. For the sake of future upgrades, you should stick with 50A. You want to choose the most common "standard" size for appliances whenever possible.



          As far as the 240/120v specification - this is because the appliance requires a neutral. It will have 3 wires - red, black and white. The voltage from red to black is 240v, and the voltage between red and white and black and white will be 120v. This allows the appliance to use 240v for the heating coils, but can run the electronics or fans with 120v. This is common on ranges and ovens, but something like a water heater has no electronics other than the heating coils so they only need two wires (red and black, typically) for 240v. In modern construction every circuit would also have a ground wire but older homes may not have that for large appliances.






          share|improve this answer













          The reason they give the option of 40A or 50A is because 50A is a standard circuit size a builder would install for a wall oven or range. However, they also want you to know that if you are running wire specifically for this oven, 40A would suffice. For the sake of future upgrades, you should stick with 50A. You want to choose the most common "standard" size for appliances whenever possible.



          As far as the 240/120v specification - this is because the appliance requires a neutral. It will have 3 wires - red, black and white. The voltage from red to black is 240v, and the voltage between red and white and black and white will be 120v. This allows the appliance to use 240v for the heating coils, but can run the electronics or fans with 120v. This is common on ranges and ovens, but something like a water heater has no electronics other than the heating coils so they only need two wires (red and black, typically) for 240v. In modern construction every circuit would also have a ground wire but older homes may not have that for large appliances.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 9 hours ago









          JPhi1618JPhi1618

          11.5k22548




          11.5k22548





















              1














              I'm not sure what your specific concern is, but here are a few points that may lend clarity:



              • The manufacturer states that a 40A circuit is adequate. Take them at their word that you won't have safety or nuisance trip problem.

              • They're offering the option of using a 50A circuit because the circuit protects the wiring leading to the device, not the device itself, and you may want the option to upgrade appliances later.

              • There is some degree of protection for the device in not drastically oversizing the circuit, but the device has integral safety mechanisms for current and thermal overload.

              • Again, the breaker protects the wiring, so be sure that the wire size you use is up to the task of whatever the breaker will allow. Do not use #8 wire on a 50A breaker, for example.





              share|improve this answer



























                1














                I'm not sure what your specific concern is, but here are a few points that may lend clarity:



                • The manufacturer states that a 40A circuit is adequate. Take them at their word that you won't have safety or nuisance trip problem.

                • They're offering the option of using a 50A circuit because the circuit protects the wiring leading to the device, not the device itself, and you may want the option to upgrade appliances later.

                • There is some degree of protection for the device in not drastically oversizing the circuit, but the device has integral safety mechanisms for current and thermal overload.

                • Again, the breaker protects the wiring, so be sure that the wire size you use is up to the task of whatever the breaker will allow. Do not use #8 wire on a 50A breaker, for example.





                share|improve this answer

























                  1












                  1








                  1







                  I'm not sure what your specific concern is, but here are a few points that may lend clarity:



                  • The manufacturer states that a 40A circuit is adequate. Take them at their word that you won't have safety or nuisance trip problem.

                  • They're offering the option of using a 50A circuit because the circuit protects the wiring leading to the device, not the device itself, and you may want the option to upgrade appliances later.

                  • There is some degree of protection for the device in not drastically oversizing the circuit, but the device has integral safety mechanisms for current and thermal overload.

                  • Again, the breaker protects the wiring, so be sure that the wire size you use is up to the task of whatever the breaker will allow. Do not use #8 wire on a 50A breaker, for example.





                  share|improve this answer













                  I'm not sure what your specific concern is, but here are a few points that may lend clarity:



                  • The manufacturer states that a 40A circuit is adequate. Take them at their word that you won't have safety or nuisance trip problem.

                  • They're offering the option of using a 50A circuit because the circuit protects the wiring leading to the device, not the device itself, and you may want the option to upgrade appliances later.

                  • There is some degree of protection for the device in not drastically oversizing the circuit, but the device has integral safety mechanisms for current and thermal overload.

                  • Again, the breaker protects the wiring, so be sure that the wire size you use is up to the task of whatever the breaker will allow. Do not use #8 wire on a 50A breaker, for example.






                  share|improve this answer












                  share|improve this answer



                  share|improve this answer










                  answered 9 hours ago









                  isherwoodisherwood

                  52.6k562137




                  52.6k562137



























                      draft saved

                      draft discarded
















































                      Thanks for contributing an answer to Home Improvement Stack Exchange!


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid


                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.

                      To learn more, see our tips on writing great answers.




                      draft saved


                      draft discarded














                      StackExchange.ready(
                      function ()
                      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f166152%2fwhy-does-my-electric-oven-present-the-option-of-40a-and-50a-breakers%23new-answer', 'question_page');

                      );

                      Post as a guest















                      Required, but never shown





















































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown

































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown







                      Popular posts from this blog

                      Canceling a color specificationRandomly assigning color to Graphics3D objects?Default color for Filling in Mathematica 9Coloring specific elements of sets with a prime modified order in an array plotHow to pick a color differing significantly from the colors already in a given color list?Detection of the text colorColor numbers based on their valueCan color schemes for use with ColorData include opacity specification?My dynamic color schemes

                      Invision Community Contents History See also References External links Navigation menuProprietaryinvisioncommunity.comIPS Community ForumsIPS Community Forumsthis blog entry"License Changes, IP.Board 3.4, and the Future""Interview -- Matt Mecham of Ibforums""CEO Invision Power Board, Matt Mecham Is a Liar, Thief!"IPB License Explanation 1.3, 1.3.1, 2.0, and 2.1ArchivedSecurity Fixes, Updates And Enhancements For IPB 1.3.1Archived"New Demo Accounts - Invision Power Services"the original"New Default Skin"the original"Invision Power Board 3.0.0 and Applications Released"the original"Archived copy"the original"Perpetual licenses being done away with""Release Notes - Invision Power Services""Introducing: IPS Community Suite 4!"Invision Community Release Notes

                      François Viète Contents Biography Work and thought Bibliography See also Notes Further reading External links Navigation menup. 21Google Bookspp. 75–77Google BooksDe thou (from University of Saint Andrews)ArchivedGoogle BooksGoogle BooksGoogle BooksGoogle booksGoogle Bookscc-parthenay.frL'histoire universelle (fr)Universal History (en)ArchivedAdsabs.harvard.eduPagesperso-orange.frArchive.orgChikara Sasaki. Descartes' mathematical thought p.259Google BooksGoogle BooksGoogle Bookspp. 152 and onwardGoogle BooksGoogle BooksScribd.comGoogle Books1257-7979Google BooksGoogle BooksGoogle BooksGoogle BooksGoogle BooksGoogle BooksGallica.bnf.frGoogle BooksGoogle Books"François Viète"Francois Viète: Father of Modern Algebraic NotationThe Lawyer and the GamblerAbout TarporleySite de Jean-Paul GuichardL'algèbre nouvelle"About the Harmonicon"cb120511976(data)1188044800000 0001 0913 5903n82164680ola2013766880073431702w6vt1sb70287374827140948071409480