How can I tell if a breaker uses both phases/legsWhat can I do about a breaker that trips frequently on a Stab-Lok panel?Do I need a ground for a new 240 volt 20 amp circuit?Intermittent (shuts off randomly) power to one leg (hot) wire in sub panelHow to tell if breaker box can handle another tandem breaker?Circuit breaker - on different phasesChinese Breaker Box (240v split-phase?) Lacks Neutral Wires and Grounding BusSeeking good method to locate short on buried AC power cableFloating service panel groundHow can I tell if this is a split bus panel with no main breaker?Adding the Sense electricity monitor to my breaker box2 wires with same neutral in a tandem circuit breaker on the same leg

Toxic, harassing lab environment

Are PMR446 walkie-talkies legal in Switzerland?

How can I tell if a breaker uses both phases/legs

Moons and messages

Did Game of Thrones end the way that George RR Martin intended?

Who were the members of the jury in the Game of Thrones finale?

Is there an idiom that means that you are in a very strong negotiation position in a negotiation?

EU rights when flight delayed so much that return is missed

Where is Jon going?

Merge pdfs sequentially

Piping the output of comand columns

Was this scene in S8E06 added because of fan reactions to S8E04?

Complications of displaced core material?

Goldfish unresponsive, what should I do?

Knight's Tour on a 7x7 Board starting from D5

Why do the i8080 I/O instructions take a byte-sized operand to determine the port?

To exponential digit growth and beyond!

The disk image is 497GB smaller than the target device

Why is std::ssize() introduced in C++20

Why A=2 and B=1 in the call signs for Spirit and Opportunity?

Storing voxels for a voxel Engine in C++

Why do testers need root cause analysis?

Could a rotating ring space station have a bolo-like extension?

Are there historical examples of audiences drawn to a work that was "so bad it's good"?



How can I tell if a breaker uses both phases/legs


What can I do about a breaker that trips frequently on a Stab-Lok panel?Do I need a ground for a new 240 volt 20 amp circuit?Intermittent (shuts off randomly) power to one leg (hot) wire in sub panelHow to tell if breaker box can handle another tandem breaker?Circuit breaker - on different phasesChinese Breaker Box (240v split-phase?) Lacks Neutral Wires and Grounding BusSeeking good method to locate short on buried AC power cableFloating service panel groundHow can I tell if this is a split bus panel with no main breaker?Adding the Sense electricity monitor to my breaker box2 wires with same neutral in a tandem circuit breaker on the same leg






.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








2















Good day.



I hooked up Sense monitor by adding a 240v breaker to my panel (bottom 2 slots on one leg). Problem is Sense has detected that my breaker is sitting on two slots that occupy the same phase/leg of the panel.



How can I tell of there is 2 slots in the electrical panel that will occupy both phase/legs so that Sense will work properly? From reading I suspect Sense monitor power needs to be connected to both phases/legs.



Panel:
Stab-lok
CAT NO. BE 116-32
MAINS 125 AMP.MAX.
120/240 VOLTS A.C.
1 Phase 3 Wire
Y24-863A



enter image description here



enter image description here










share|improve this question









New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.














  • 1





    If it is a 240v (two pole) breaker that is designed for that panel, it should hit both legs. If you test the voltage between the two lugs on the breaker is it 240v?

    – JPhi1618
    8 hours ago











  • Added some images to original post.

    – Alister55
    4 hours ago











  • Sense Response: we noticed that your Sense power wires are drawing from the same phase, or leg. of your electrical panel. It's possible that the power wires were either installed on a tandem breaker or, if you installed on a 240V breaker, Sense is sitting on two slots that occupy the same phase/leg of the panel. While the 240V breaker does ensure that it draws power from two different slots on the panel, depending on where it is placed, those two slots can be drawing from the same phase. To put it into perspective, this is what the phase pattern of the left side of your panel could look like:

    – Alister55
    4 hours ago











  • phase A phase B phase A phase B phase B phase B If your double breaker is attached on a spot where the phase repeats (consecutive phase A), such as towards the bottom, you may run into the issue I've described. I cannot say for sure what your panel phase map is, but you should refer to what is printed on the panel, or reach out to your electrician.

    – Alister55
    4 hours ago






  • 1





    This is a straight up guess, but it looks like all of your other 240v breakers straddle one of those thick lines on the breaker numbering label. So the order of the slots could be AA|BB|AA|BB.

    – JPhi1618
    4 hours ago

















2















Good day.



I hooked up Sense monitor by adding a 240v breaker to my panel (bottom 2 slots on one leg). Problem is Sense has detected that my breaker is sitting on two slots that occupy the same phase/leg of the panel.



How can I tell of there is 2 slots in the electrical panel that will occupy both phase/legs so that Sense will work properly? From reading I suspect Sense monitor power needs to be connected to both phases/legs.



Panel:
Stab-lok
CAT NO. BE 116-32
MAINS 125 AMP.MAX.
120/240 VOLTS A.C.
1 Phase 3 Wire
Y24-863A



enter image description here



enter image description here










share|improve this question









New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.














  • 1





    If it is a 240v (two pole) breaker that is designed for that panel, it should hit both legs. If you test the voltage between the two lugs on the breaker is it 240v?

    – JPhi1618
    8 hours ago











  • Added some images to original post.

    – Alister55
    4 hours ago











  • Sense Response: we noticed that your Sense power wires are drawing from the same phase, or leg. of your electrical panel. It's possible that the power wires were either installed on a tandem breaker or, if you installed on a 240V breaker, Sense is sitting on two slots that occupy the same phase/leg of the panel. While the 240V breaker does ensure that it draws power from two different slots on the panel, depending on where it is placed, those two slots can be drawing from the same phase. To put it into perspective, this is what the phase pattern of the left side of your panel could look like:

    – Alister55
    4 hours ago











  • phase A phase B phase A phase B phase B phase B If your double breaker is attached on a spot where the phase repeats (consecutive phase A), such as towards the bottom, you may run into the issue I've described. I cannot say for sure what your panel phase map is, but you should refer to what is printed on the panel, or reach out to your electrician.

    – Alister55
    4 hours ago






  • 1





    This is a straight up guess, but it looks like all of your other 240v breakers straddle one of those thick lines on the breaker numbering label. So the order of the slots could be AA|BB|AA|BB.

    – JPhi1618
    4 hours ago













2












2








2








Good day.



I hooked up Sense monitor by adding a 240v breaker to my panel (bottom 2 slots on one leg). Problem is Sense has detected that my breaker is sitting on two slots that occupy the same phase/leg of the panel.



How can I tell of there is 2 slots in the electrical panel that will occupy both phase/legs so that Sense will work properly? From reading I suspect Sense monitor power needs to be connected to both phases/legs.



Panel:
Stab-lok
CAT NO. BE 116-32
MAINS 125 AMP.MAX.
120/240 VOLTS A.C.
1 Phase 3 Wire
Y24-863A



enter image description here



enter image description here










share|improve this question









New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











Good day.



I hooked up Sense monitor by adding a 240v breaker to my panel (bottom 2 slots on one leg). Problem is Sense has detected that my breaker is sitting on two slots that occupy the same phase/leg of the panel.



How can I tell of there is 2 slots in the electrical panel that will occupy both phase/legs so that Sense will work properly? From reading I suspect Sense monitor power needs to be connected to both phases/legs.



Panel:
Stab-lok
CAT NO. BE 116-32
MAINS 125 AMP.MAX.
120/240 VOLTS A.C.
1 Phase 3 Wire
Y24-863A



enter image description here



enter image description here







electrical electrical-panel






share|improve this question









New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.










share|improve this question









New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.








share|improve this question




share|improve this question








edited 4 hours ago







Alister55













New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.








asked 8 hours ago









Alister55Alister55

112




112




New contributor



Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




New contributor




Alister55 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









  • 1





    If it is a 240v (two pole) breaker that is designed for that panel, it should hit both legs. If you test the voltage between the two lugs on the breaker is it 240v?

    – JPhi1618
    8 hours ago











  • Added some images to original post.

    – Alister55
    4 hours ago











  • Sense Response: we noticed that your Sense power wires are drawing from the same phase, or leg. of your electrical panel. It's possible that the power wires were either installed on a tandem breaker or, if you installed on a 240V breaker, Sense is sitting on two slots that occupy the same phase/leg of the panel. While the 240V breaker does ensure that it draws power from two different slots on the panel, depending on where it is placed, those two slots can be drawing from the same phase. To put it into perspective, this is what the phase pattern of the left side of your panel could look like:

    – Alister55
    4 hours ago











  • phase A phase B phase A phase B phase B phase B If your double breaker is attached on a spot where the phase repeats (consecutive phase A), such as towards the bottom, you may run into the issue I've described. I cannot say for sure what your panel phase map is, but you should refer to what is printed on the panel, or reach out to your electrician.

    – Alister55
    4 hours ago






  • 1





    This is a straight up guess, but it looks like all of your other 240v breakers straddle one of those thick lines on the breaker numbering label. So the order of the slots could be AA|BB|AA|BB.

    – JPhi1618
    4 hours ago












  • 1





    If it is a 240v (two pole) breaker that is designed for that panel, it should hit both legs. If you test the voltage between the two lugs on the breaker is it 240v?

    – JPhi1618
    8 hours ago











  • Added some images to original post.

    – Alister55
    4 hours ago











  • Sense Response: we noticed that your Sense power wires are drawing from the same phase, or leg. of your electrical panel. It's possible that the power wires were either installed on a tandem breaker or, if you installed on a 240V breaker, Sense is sitting on two slots that occupy the same phase/leg of the panel. While the 240V breaker does ensure that it draws power from two different slots on the panel, depending on where it is placed, those two slots can be drawing from the same phase. To put it into perspective, this is what the phase pattern of the left side of your panel could look like:

    – Alister55
    4 hours ago











  • phase A phase B phase A phase B phase B phase B If your double breaker is attached on a spot where the phase repeats (consecutive phase A), such as towards the bottom, you may run into the issue I've described. I cannot say for sure what your panel phase map is, but you should refer to what is printed on the panel, or reach out to your electrician.

    – Alister55
    4 hours ago






  • 1





    This is a straight up guess, but it looks like all of your other 240v breakers straddle one of those thick lines on the breaker numbering label. So the order of the slots could be AA|BB|AA|BB.

    – JPhi1618
    4 hours ago







1




1





If it is a 240v (two pole) breaker that is designed for that panel, it should hit both legs. If you test the voltage between the two lugs on the breaker is it 240v?

– JPhi1618
8 hours ago





If it is a 240v (two pole) breaker that is designed for that panel, it should hit both legs. If you test the voltage between the two lugs on the breaker is it 240v?

– JPhi1618
8 hours ago













Added some images to original post.

– Alister55
4 hours ago





Added some images to original post.

– Alister55
4 hours ago













Sense Response: we noticed that your Sense power wires are drawing from the same phase, or leg. of your electrical panel. It's possible that the power wires were either installed on a tandem breaker or, if you installed on a 240V breaker, Sense is sitting on two slots that occupy the same phase/leg of the panel. While the 240V breaker does ensure that it draws power from two different slots on the panel, depending on where it is placed, those two slots can be drawing from the same phase. To put it into perspective, this is what the phase pattern of the left side of your panel could look like:

– Alister55
4 hours ago





Sense Response: we noticed that your Sense power wires are drawing from the same phase, or leg. of your electrical panel. It's possible that the power wires were either installed on a tandem breaker or, if you installed on a 240V breaker, Sense is sitting on two slots that occupy the same phase/leg of the panel. While the 240V breaker does ensure that it draws power from two different slots on the panel, depending on where it is placed, those two slots can be drawing from the same phase. To put it into perspective, this is what the phase pattern of the left side of your panel could look like:

– Alister55
4 hours ago













phase A phase B phase A phase B phase B phase B If your double breaker is attached on a spot where the phase repeats (consecutive phase A), such as towards the bottom, you may run into the issue I've described. I cannot say for sure what your panel phase map is, but you should refer to what is printed on the panel, or reach out to your electrician.

– Alister55
4 hours ago





phase A phase B phase A phase B phase B phase B If your double breaker is attached on a spot where the phase repeats (consecutive phase A), such as towards the bottom, you may run into the issue I've described. I cannot say for sure what your panel phase map is, but you should refer to what is printed on the panel, or reach out to your electrician.

– Alister55
4 hours ago




1




1





This is a straight up guess, but it looks like all of your other 240v breakers straddle one of those thick lines on the breaker numbering label. So the order of the slots could be AA|BB|AA|BB.

– JPhi1618
4 hours ago





This is a straight up guess, but it looks like all of your other 240v breakers straddle one of those thick lines on the breaker numbering label. So the order of the slots could be AA|BB|AA|BB.

– JPhi1618
4 hours ago










1 Answer
1






active

oldest

votes


















4














Stab-Lok is a PROBLEM



See, for example, What can I do about a breaker that trips frequently on a Stab-Lok panel?



So first read up on Stab-Lok, post a picture of your panel (the pros will recognize it and tell you if it really is a fire hazard, etc.) and determine if this is a concern. If it is a real concern, then dealing with replacement is a much higher priority than hooking up the Sense monitor.



How it SHOULD Work



On many panels (I don't know if Stab-Lok is supposed to work this way or not), a true double (240V) breaker will always hit both legs. The exception is a double-stuff breaker, where it is really two-breakers-in-one. In that case, it normally only hits one leg, and the exception is if it can actually be 1/2 of one leg and 1/2 of the other leg. But that, as I understand it, is only on certain panels where you can have a quad == 4 in one, but really 4 in 2 - i.e., a double-space breaker that has 4 individual breakers, two on one leg, two on the other leg, with the result that the inner breakers can function together as a "double 240V breaker".



FIRST FIGURE OUT THE STAB-LOK!






share|improve this answer


















  • 1





    I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

    – Alister55
    3 hours ago






  • 1





    "Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

    – manassehkatz
    3 hours ago






  • 1





    Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

    – Alister55
    3 hours ago











Your Answer








StackExchange.ready(function()
var channelOptions =
tags: "".split(" "),
id: "73"
;
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function()
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled)
StackExchange.using("snippets", function()
createEditor();
);

else
createEditor();

);

function createEditor()
StackExchange.prepareEditor(
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader:
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
,
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
);



);






Alister55 is a new contributor. Be nice, and check out our Code of Conduct.









draft saved

draft discarded


















StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f165525%2fhow-can-i-tell-if-a-breaker-uses-both-phases-legs%23new-answer', 'question_page');

);

Post as a guest















Required, but never shown

























1 Answer
1






active

oldest

votes








1 Answer
1






active

oldest

votes









active

oldest

votes






active

oldest

votes









4














Stab-Lok is a PROBLEM



See, for example, What can I do about a breaker that trips frequently on a Stab-Lok panel?



So first read up on Stab-Lok, post a picture of your panel (the pros will recognize it and tell you if it really is a fire hazard, etc.) and determine if this is a concern. If it is a real concern, then dealing with replacement is a much higher priority than hooking up the Sense monitor.



How it SHOULD Work



On many panels (I don't know if Stab-Lok is supposed to work this way or not), a true double (240V) breaker will always hit both legs. The exception is a double-stuff breaker, where it is really two-breakers-in-one. In that case, it normally only hits one leg, and the exception is if it can actually be 1/2 of one leg and 1/2 of the other leg. But that, as I understand it, is only on certain panels where you can have a quad == 4 in one, but really 4 in 2 - i.e., a double-space breaker that has 4 individual breakers, two on one leg, two on the other leg, with the result that the inner breakers can function together as a "double 240V breaker".



FIRST FIGURE OUT THE STAB-LOK!






share|improve this answer


















  • 1





    I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

    – Alister55
    3 hours ago






  • 1





    "Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

    – manassehkatz
    3 hours ago






  • 1





    Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

    – Alister55
    3 hours ago















4














Stab-Lok is a PROBLEM



See, for example, What can I do about a breaker that trips frequently on a Stab-Lok panel?



So first read up on Stab-Lok, post a picture of your panel (the pros will recognize it and tell you if it really is a fire hazard, etc.) and determine if this is a concern. If it is a real concern, then dealing with replacement is a much higher priority than hooking up the Sense monitor.



How it SHOULD Work



On many panels (I don't know if Stab-Lok is supposed to work this way or not), a true double (240V) breaker will always hit both legs. The exception is a double-stuff breaker, where it is really two-breakers-in-one. In that case, it normally only hits one leg, and the exception is if it can actually be 1/2 of one leg and 1/2 of the other leg. But that, as I understand it, is only on certain panels where you can have a quad == 4 in one, but really 4 in 2 - i.e., a double-space breaker that has 4 individual breakers, two on one leg, two on the other leg, with the result that the inner breakers can function together as a "double 240V breaker".



FIRST FIGURE OUT THE STAB-LOK!






share|improve this answer


















  • 1





    I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

    – Alister55
    3 hours ago






  • 1





    "Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

    – manassehkatz
    3 hours ago






  • 1





    Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

    – Alister55
    3 hours ago













4












4








4







Stab-Lok is a PROBLEM



See, for example, What can I do about a breaker that trips frequently on a Stab-Lok panel?



So first read up on Stab-Lok, post a picture of your panel (the pros will recognize it and tell you if it really is a fire hazard, etc.) and determine if this is a concern. If it is a real concern, then dealing with replacement is a much higher priority than hooking up the Sense monitor.



How it SHOULD Work



On many panels (I don't know if Stab-Lok is supposed to work this way or not), a true double (240V) breaker will always hit both legs. The exception is a double-stuff breaker, where it is really two-breakers-in-one. In that case, it normally only hits one leg, and the exception is if it can actually be 1/2 of one leg and 1/2 of the other leg. But that, as I understand it, is only on certain panels where you can have a quad == 4 in one, but really 4 in 2 - i.e., a double-space breaker that has 4 individual breakers, two on one leg, two on the other leg, with the result that the inner breakers can function together as a "double 240V breaker".



FIRST FIGURE OUT THE STAB-LOK!






share|improve this answer













Stab-Lok is a PROBLEM



See, for example, What can I do about a breaker that trips frequently on a Stab-Lok panel?



So first read up on Stab-Lok, post a picture of your panel (the pros will recognize it and tell you if it really is a fire hazard, etc.) and determine if this is a concern. If it is a real concern, then dealing with replacement is a much higher priority than hooking up the Sense monitor.



How it SHOULD Work



On many panels (I don't know if Stab-Lok is supposed to work this way or not), a true double (240V) breaker will always hit both legs. The exception is a double-stuff breaker, where it is really two-breakers-in-one. In that case, it normally only hits one leg, and the exception is if it can actually be 1/2 of one leg and 1/2 of the other leg. But that, as I understand it, is only on certain panels where you can have a quad == 4 in one, but really 4 in 2 - i.e., a double-space breaker that has 4 individual breakers, two on one leg, two on the other leg, with the result that the inner breakers can function together as a "double 240V breaker".



FIRST FIGURE OUT THE STAB-LOK!







share|improve this answer












share|improve this answer



share|improve this answer










answered 8 hours ago









manassehkatzmanassehkatz

12.3k1843




12.3k1843







  • 1





    I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

    – Alister55
    3 hours ago






  • 1





    "Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

    – manassehkatz
    3 hours ago






  • 1





    Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

    – Alister55
    3 hours ago












  • 1





    I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

    – Alister55
    3 hours ago






  • 1





    "Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

    – manassehkatz
    3 hours ago






  • 1





    Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

    – Alister55
    3 hours ago







1




1





I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

– Alister55
3 hours ago





I will have a read on the Stab-lok issue to be sure it isn't a fire hazard. Hate the idea of having to replace the panel but better than the house burning down. I would think that it's not a problem since the panel has been inspected but because it's labeled inspected for the garage power maybe they didn't look into this panel. As far as the Sense issue goes, I noticed an circuit image on the inside of the panel cover I pulled off and will look at that and post if I can make sense of it.

– Alister55
3 hours ago




1




1





"Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

– manassehkatz
3 hours ago





"Inspected" can mean: "Inspected at time of initial installation" - which would mean nothing because at the time the hazards were not well known.

– manassehkatz
3 hours ago




1




1





Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

– Alister55
3 hours ago





Date says inspected 1991. Still reading about the issue and it's a little concerning. Thinking maybe I will contact a local electrician and just have the entire panel replaced.

– Alister55
3 hours ago










Alister55 is a new contributor. Be nice, and check out our Code of Conduct.









draft saved

draft discarded


















Alister55 is a new contributor. Be nice, and check out our Code of Conduct.












Alister55 is a new contributor. Be nice, and check out our Code of Conduct.











Alister55 is a new contributor. Be nice, and check out our Code of Conduct.














Thanks for contributing an answer to Home Improvement Stack Exchange!


  • Please be sure to answer the question. Provide details and share your research!

But avoid


  • Asking for help, clarification, or responding to other answers.

  • Making statements based on opinion; back them up with references or personal experience.

To learn more, see our tips on writing great answers.




draft saved


draft discarded














StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f165525%2fhow-can-i-tell-if-a-breaker-uses-both-phases-legs%23new-answer', 'question_page');

);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown







Popular posts from this blog

Invision Community Contents History See also References External links Navigation menuProprietaryinvisioncommunity.comIPS Community ForumsIPS Community Forumsthis blog entry"License Changes, IP.Board 3.4, and the Future""Interview -- Matt Mecham of Ibforums""CEO Invision Power Board, Matt Mecham Is a Liar, Thief!"IPB License Explanation 1.3, 1.3.1, 2.0, and 2.1ArchivedSecurity Fixes, Updates And Enhancements For IPB 1.3.1Archived"New Demo Accounts - Invision Power Services"the original"New Default Skin"the original"Invision Power Board 3.0.0 and Applications Released"the original"Archived copy"the original"Perpetual licenses being done away with""Release Notes - Invision Power Services""Introducing: IPS Community Suite 4!"Invision Community Release Notes

Canceling a color specificationRandomly assigning color to Graphics3D objects?Default color for Filling in Mathematica 9Coloring specific elements of sets with a prime modified order in an array plotHow to pick a color differing significantly from the colors already in a given color list?Detection of the text colorColor numbers based on their valueCan color schemes for use with ColorData include opacity specification?My dynamic color schemes

Ласкавець круглолистий Зміст Опис | Поширення | Галерея | Примітки | Посилання | Навігаційне меню58171138361-22960890446Bupleurum rotundifoliumEuro+Med PlantbasePlants of the World Online — Kew ScienceGermplasm Resources Information Network (GRIN)Ласкавецькн. VI : Літери Ком — Левиправивши або дописавши її