Can the ground attached to neutral fool a receptacle tester?Can I ground my workbench using an unused outlet's neutral?Does a neutral-to-ground voltage of 0.0 indicate a bootleg ground?Outlet with ground wire attached to socket ground and neutralOdd Problem Testing Series OutletsGFCI Outlet Trips with Receptacle TEST Button, but not with GFCI Outlet Tester ToolGFCI tester doesn't trip GFCI. Bootleg ground?Grounding issues and ground testerWhy is neutral wired to ground at this switch?Trying to add an outlet on other side of wall, 3 pairs of white/black wires and groundIf a receptacle is added from a switch box, will the receptacle only work when the switch is off?

Multirow in tabularx?

What is the maximum number of PC-controlled undead?

Is refreshing multiple times a test case for web applications?

Is there a way to unplug the Raspberry pi safely without shutting down

What game uses dice with sides powers of 2?

function evaluation - I don't get it

Was the 2019 Lion King film made through motion capture?

Plausibility of Ice Eaters in the Arctic

During the Space Shuttle Columbia Disaster of 2003, Why Did The Flight Director Say, "Lock the doors."?

As a 16 year old, how can I keep my money safe from my mother?

Should you play baroque pieces a semitone lower?

Wherein the Shatapatha Brahmana it was mentioned about 8.64 lakh alphabets in Vedas?

A tool to replace all words with antonyms

Trying to write a shell script that keeps testing a server remotely, but it keeps falling in else statement when I logout

Continuous vertical line using booktabs in tabularx table?

Acceptable to cut steak before searing?

changing number of arguments to a function in secondary evaluation

Can a fight scene, component-wise, be too complex and complicated?

First amendment and employment: Can a police department terminate an officer for speech?

Visa National - No Exit Stamp From France on Return to the UK

Three legged NOT gate? What is this symbol?

What should I call bands of armed men in Medieval Times?

Blocking people from taking pictures of me with smartphone

Can you castle with a "ghost" rook?



Can the ground attached to neutral fool a receptacle tester?


Can I ground my workbench using an unused outlet's neutral?Does a neutral-to-ground voltage of 0.0 indicate a bootleg ground?Outlet with ground wire attached to socket ground and neutralOdd Problem Testing Series OutletsGFCI Outlet Trips with Receptacle TEST Button, but not with GFCI Outlet Tester ToolGFCI tester doesn't trip GFCI. Bootleg ground?Grounding issues and ground testerWhy is neutral wired to ground at this switch?Trying to add an outlet on other side of wall, 3 pairs of white/black wires and groundIf a receptacle is added from a switch box, will the receptacle only work when the switch is off?






.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








2















I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here










share|improve this question



















  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    4 hours ago


















2















I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here










share|improve this question



















  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    4 hours ago














2












2








2








I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here










share|improve this question














I'm using a basic outlet tester like the one from picture below. Let's say someone wired the ground to the neutral in some outlet, to provide a fake ground. What would the tester report? Would it be "CORRECT" or would it be something else?



In case it reports "CORRECT" (wrongly, of course), is there some easy way to test that the ground is fake? By easy I mean not having to open the outlet...



enter image description here







electrical receptacle grounding neutral grounding-and-bonding






share|improve this question













share|improve this question











share|improve this question




share|improve this question










asked 9 hours ago









fernacolofernacolo

1591 silver badge5 bronze badges




1591 silver badge5 bronze badges










  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    4 hours ago













  • 1





    put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

    – jsotola
    4 hours ago








1




1





put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

– jsotola
4 hours ago






put a heavy load on the power outlet ... measure the voltage between neutral and ground ... zero voltage indicates that the two are shorted at the plug

– jsotola
4 hours ago











3 Answers
3






active

oldest

votes


















4














The tester will show "correct". Opening the outlet is the only way to check it that I know of.






share|improve this answer
































    4














    The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



    What do the Lights Indicate?



    These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):



    • Hot to Ground

    This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



    Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



    That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.



    • Hot to Neutral

    This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.



    • Neutral to Ground

    Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



    What do the Light Combinations Mean?



    There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



    Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.



    • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


    • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


    • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


    • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


    • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


    • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.






    share|improve this answer


































      1














      Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



      Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



      So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:



      • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

      • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.

      With old wiring there's no substitute for opening it up and having a look.






      share|improve this answer





























        Your Answer








        StackExchange.ready(function()
        var channelOptions =
        tags: "".split(" "),
        id: "73"
        ;
        initTagRenderer("".split(" "), "".split(" "), channelOptions);

        StackExchange.using("externalEditor", function()
        // Have to fire editor after snippets, if snippets enabled
        if (StackExchange.settings.snippets.snippetsEnabled)
        StackExchange.using("snippets", function()
        createEditor();
        );

        else
        createEditor();

        );

        function createEditor()
        StackExchange.prepareEditor(
        heartbeatType: 'answer',
        autoActivateHeartbeat: false,
        convertImagesToLinks: false,
        noModals: true,
        showLowRepImageUploadWarning: true,
        reputationToPostImages: null,
        bindNavPrevention: true,
        postfix: "",
        imageUploader:
        brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
        contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
        allowUrls: true
        ,
        noCode: true, onDemand: true,
        discardSelector: ".discard-answer"
        ,immediatelyShowMarkdownHelp:true
        );



        );













        draft saved

        draft discarded


















        StackExchange.ready(
        function ()
        StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f171022%2fcan-the-ground-attached-to-neutral-fool-a-receptacle-tester%23new-answer', 'question_page');

        );

        Post as a guest















        Required, but never shown

























        3 Answers
        3






        active

        oldest

        votes








        3 Answers
        3






        active

        oldest

        votes









        active

        oldest

        votes






        active

        oldest

        votes









        4














        The tester will show "correct". Opening the outlet is the only way to check it that I know of.






        share|improve this answer





























          4














          The tester will show "correct". Opening the outlet is the only way to check it that I know of.






          share|improve this answer



























            4












            4








            4







            The tester will show "correct". Opening the outlet is the only way to check it that I know of.






            share|improve this answer













            The tester will show "correct". Opening the outlet is the only way to check it that I know of.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered 8 hours ago









            JACKJACK

            1,44110 bronze badges




            1,44110 bronze badges


























                4














                The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                What do the Lights Indicate?



                These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):



                • Hot to Ground

                This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.



                • Hot to Neutral

                This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.



                • Neutral to Ground

                Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                What do the Light Combinations Mean?



                There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.



                • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.






                share|improve this answer































                  4














                  The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                  What do the Lights Indicate?



                  These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):



                  • Hot to Ground

                  This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                  Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                  That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.



                  • Hot to Neutral

                  This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.



                  • Neutral to Ground

                  Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                  What do the Light Combinations Mean?



                  There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                  Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.



                  • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                  • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                  • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                  • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                  • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                  • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.






                  share|improve this answer





























                    4












                    4








                    4







                    The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                    What do the Lights Indicate?



                    These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):



                    • Hot to Ground

                    This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                    Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                    That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.



                    • Hot to Neutral

                    This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.



                    • Neutral to Ground

                    Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                    What do the Light Combinations Mean?



                    There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                    Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.



                    • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                    • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                    • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                    • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                    • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                    • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.






                    share|improve this answer















                    The tester can't tell the difference. One way to look at is that electrically, since neutral and ground are already bonded at one location (normally the main panel), the electrons don't know the difference. But the other way to think about it is to look at what the tester is actually doing.



                    What do the Lights Indicate?



                    These testers are actually 3 simple lights connected as follows (left to right on your particular tester, others may vary):



                    • Hot to Ground

                    This will light up provided that Hot is indeed Hot (and not Neutral) and Ground is functional.



                    Note that Ground being functional in this context does not mean "connected to a water pipe or rebar or a ground rod", though that alone might be enough. It means "ground connected to neutral in the main panel".



                    That also means that if Ground is connected directly to neutral in this receptacle box, the tester does not see that as a problem.



                    • Hot to Neutral

                    This will light up provided that Hot is indeed Hot (and not Neutral) and Neutral is functional.



                    • Neutral to Ground

                    Since Neutral and Ground are bonded in the main panel, this light is normally off. Connecting them inside the receptacle box won't make any difference. Where this does light up is if something else is really messed up so that current flows between neutral and ground. The most likely scenarios are Hot swapped with either Neutral or Ground, so the tester "identifies" those conditions but those are really not guarantees as there are other possible situations.



                    What do the Light Combinations Mean?



                    There are 8 possible combinations. But "all on" would be really strange (but possible if someone wires a 120V receptacle to a 240V breaker) so that is not included. The other combination not included is Off, Off, On. That would mean current flowing only between Ground and Neutral (the exact opposite of this question), and no current flowing between Hot & Neutral or between Hot & Ground, which would be pretty hard to do (Open Hot + Hot/Neutral swapped?)



                    Just remember, the titles assigned are based on the most common scenarios but are not the only possible problems.



                    • Off, On, Off = Open Ground - Hot to Neutral but no Hot to Ground


                    • On, Off, Off = Open Neutral - Hot to Ground but no Hot to Neutral


                    • Off, Off, Off = Open Hot - But really means "nothing at all" - e.g., could be "Open Ground + Open Neutral but Hot OK" - so don't assume this means there is no hot wire present - that could be a deadly mistake!


                    • On, Off, On = Hot/Ground Reverse - Hot to Ground OK, but not Hot to Neutral, so the likely situation is that the Hot & Ground wires are reversed but it could be something else.


                    • Off, On, On = Hot/Neutral Reverse - Hot to Neutral OK, but not Hot to Ground, so the likely situation is that the Hot & Neutral wires are reversed but it could be something else.


                    • On, On, Off = Correct - Except, it really only tells you that Hot is in the right place and that all Ground & Neutral are, collectively, correct. It does not tell you, for example, if Ground & Neutral are reversed or, as originally asked, if Ground & Neutral are combined.







                    share|improve this answer














                    share|improve this answer



                    share|improve this answer








                    edited 2 hours ago

























                    answered 6 hours ago









                    manassehkatzmanassehkatz

                    16.1k1 gold badge23 silver badges50 bronze badges




                    16.1k1 gold badge23 silver badges50 bronze badges
























                        1














                        Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                        Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                        So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:



                        • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                        • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.

                        With old wiring there's no substitute for opening it up and having a look.






                        share|improve this answer































                          1














                          Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                          Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                          So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:



                          • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                          • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.

                          With old wiring there's no substitute for opening it up and having a look.






                          share|improve this answer





























                            1












                            1








                            1







                            Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                            Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                            So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:



                            • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                            • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.

                            With old wiring there's no substitute for opening it up and having a look.






                            share|improve this answer















                            Yes, it will misread. Because magic-8-ball testers are built for one thing: a quick pass/fail test for brand new wiring you just installed.



                            Obviously, in new wiring, you don't have a bunch of the kinds of problems you have in old wiring, like people bootlegging ground off neutral. The device is simply not made to solve those problems.



                            So if you misuse the tool to test old wiring, the reports (what it says on the label) will often be misleading, and will send you on wild goose chases. That's why I call it a magic 8-ball tester! An actual magic-8-ball would be about as reliable. It is useful in two ways:



                            • The lights themselves can give you hints (provided you know how they are connected, see manassehkatz's discussion)

                            • The "GFCI test" button can be helpful when testing downline receptacles fed off a GFCI elsewhere.

                            With old wiring there's no substitute for opening it up and having a look.







                            share|improve this answer














                            share|improve this answer



                            share|improve this answer








                            edited 4 hours ago

























                            answered 5 hours ago









                            HarperHarper

                            91.2k6 gold badges66 silver badges188 bronze badges




                            91.2k6 gold badges66 silver badges188 bronze badges






























                                draft saved

                                draft discarded
















































                                Thanks for contributing an answer to Home Improvement Stack Exchange!


                                • Please be sure to answer the question. Provide details and share your research!

                                But avoid


                                • Asking for help, clarification, or responding to other answers.

                                • Making statements based on opinion; back them up with references or personal experience.

                                To learn more, see our tips on writing great answers.




                                draft saved


                                draft discarded














                                StackExchange.ready(
                                function ()
                                StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f171022%2fcan-the-ground-attached-to-neutral-fool-a-receptacle-tester%23new-answer', 'question_page');

                                );

                                Post as a guest















                                Required, but never shown





















































                                Required, but never shown














                                Required, but never shown












                                Required, but never shown







                                Required, but never shown

































                                Required, but never shown














                                Required, but never shown












                                Required, but never shown







                                Required, but never shown







                                Popular posts from this blog

                                Invision Community Contents History See also References External links Navigation menuProprietaryinvisioncommunity.comIPS Community ForumsIPS Community Forumsthis blog entry"License Changes, IP.Board 3.4, and the Future""Interview -- Matt Mecham of Ibforums""CEO Invision Power Board, Matt Mecham Is a Liar, Thief!"IPB License Explanation 1.3, 1.3.1, 2.0, and 2.1ArchivedSecurity Fixes, Updates And Enhancements For IPB 1.3.1Archived"New Demo Accounts - Invision Power Services"the original"New Default Skin"the original"Invision Power Board 3.0.0 and Applications Released"the original"Archived copy"the original"Perpetual licenses being done away with""Release Notes - Invision Power Services""Introducing: IPS Community Suite 4!"Invision Community Release Notes

                                Canceling a color specificationRandomly assigning color to Graphics3D objects?Default color for Filling in Mathematica 9Coloring specific elements of sets with a prime modified order in an array plotHow to pick a color differing significantly from the colors already in a given color list?Detection of the text colorColor numbers based on their valueCan color schemes for use with ColorData include opacity specification?My dynamic color schemes

                                Ласкавець круглолистий Зміст Опис | Поширення | Галерея | Примітки | Посилання | Навігаційне меню58171138361-22960890446Bupleurum rotundifoliumEuro+Med PlantbasePlants of the World Online — Kew ScienceGermplasm Resources Information Network (GRIN)Ласкавецькн. VI : Літери Ком — Левиправивши або дописавши її