Connect neutrals together in 3-gang box (load side) with 3x 3-way switches?What is the right way to connect 7 conductors in an electrical box?In a multi-gang box, are neutral wires paired with specific hot wires?How do I wire three 3-way switches in one gang box to three switches in another box?Adjacent light circuit is inadvertently controlled by four-way switch wiringReplacing three way switches with insteonShould I connect one cable to each outlet in a two-gang box?3 way switches with switch load at each endContinuous power between multi-gang boxes with 3 way switches3-way switch wired with jumper between load and travellerConvert 2 adjacent double gang box to 4 gang box; what are these extra wires?

Is this more than a packing puzzle?

Are L-functions uniquely determined by their values at negative integers?

How would someone destroy a black hole that’s at the centre of a planet?

Why do they not say "The Baby"

(algebraic topology) question about the cellular approximation theorem

Would letting a multiclass character rebuild their character to be single-classed be game-breaking?

Does entangle require vegetation?

Construct a pentagon avoiding compass use

Redox reactions redefined

Are lithium batteries allowed in the International Space Station?

Ezek. 24:1-2, "Again in the ninth year, in the tenth month, in the tenth day of the month, ...." Which month was the tenth month?

What is the German equivalent of 干物女 (dried fish woman)?

Align by center of symbol

What impact would a dragon the size of Asia have on the environment?

Is it rude to tell recruiters I would only change jobs for a better salary?

Do native speakers use ZVE or CPU?

Remove intersect line for one circle using venndiagram2sets

do not have power to all my breakers

Why does the Earth have a z-component at the start of the J2000 epoch?

Can a continent naturally split into two distant parts within a week?

Why is the collector feedback bias popular in electret-mic preamp circuits?

I quit, and boss offered me 3 month "grace period" where I could still come back

Is `curl something | sudo bash -` a reasonably safe installation method?

Filtering fine silt/mud from water (not necessarily bacteria etc.)



Connect neutrals together in 3-gang box (load side) with 3x 3-way switches?


What is the right way to connect 7 conductors in an electrical box?In a multi-gang box, are neutral wires paired with specific hot wires?How do I wire three 3-way switches in one gang box to three switches in another box?Adjacent light circuit is inadvertently controlled by four-way switch wiringReplacing three way switches with insteonShould I connect one cable to each outlet in a two-gang box?3 way switches with switch load at each endContinuous power between multi-gang boxes with 3 way switches3-way switch wired with jumper between load and travellerConvert 2 adjacent double gang box to 4 gang box; what are these extra wires?






.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








1















I have 2x 3-gang boxes, each with 3x 3-way switches in each box. All are on the same 15A breaker.



I have wired them together and I'm just connecting the switches now. I have:



 -------- ---------
BREAKER --14/2-- |3x-3WAY| --3x14/3-- |3x 3-WAY| ---3x14/2-- LIGHTS
--------- ---------


The 3-gang boxes are connected with 3 runs of 14/3 cable.



My question is: should I splice the neutrals together (and the grounds) at the second 3-gang box (load side)? It seems like it doesn't matter, since they could just as well be going to 3x 1-gang boxes on the load side in which case they would NOT be connected.



To clarify - I'm not asking if I should connect neutral to ground (I know I shouldn't do that). I'm asking if I should connect all the neutrals together and pigtail off that or just treat each switch independently on the load side.



Is there a standard way to do it?










share|improve this question









New contributor



Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.

























    1















    I have 2x 3-gang boxes, each with 3x 3-way switches in each box. All are on the same 15A breaker.



    I have wired them together and I'm just connecting the switches now. I have:



     -------- ---------
    BREAKER --14/2-- |3x-3WAY| --3x14/3-- |3x 3-WAY| ---3x14/2-- LIGHTS
    --------- ---------


    The 3-gang boxes are connected with 3 runs of 14/3 cable.



    My question is: should I splice the neutrals together (and the grounds) at the second 3-gang box (load side)? It seems like it doesn't matter, since they could just as well be going to 3x 1-gang boxes on the load side in which case they would NOT be connected.



    To clarify - I'm not asking if I should connect neutral to ground (I know I shouldn't do that). I'm asking if I should connect all the neutrals together and pigtail off that or just treat each switch independently on the load side.



    Is there a standard way to do it?










    share|improve this question









    New contributor



    Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
    Check out our Code of Conduct.





















      1












      1








      1








      I have 2x 3-gang boxes, each with 3x 3-way switches in each box. All are on the same 15A breaker.



      I have wired them together and I'm just connecting the switches now. I have:



       -------- ---------
      BREAKER --14/2-- |3x-3WAY| --3x14/3-- |3x 3-WAY| ---3x14/2-- LIGHTS
      --------- ---------


      The 3-gang boxes are connected with 3 runs of 14/3 cable.



      My question is: should I splice the neutrals together (and the grounds) at the second 3-gang box (load side)? It seems like it doesn't matter, since they could just as well be going to 3x 1-gang boxes on the load side in which case they would NOT be connected.



      To clarify - I'm not asking if I should connect neutral to ground (I know I shouldn't do that). I'm asking if I should connect all the neutrals together and pigtail off that or just treat each switch independently on the load side.



      Is there a standard way to do it?










      share|improve this question









      New contributor



      Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.











      I have 2x 3-gang boxes, each with 3x 3-way switches in each box. All are on the same 15A breaker.



      I have wired them together and I'm just connecting the switches now. I have:



       -------- ---------
      BREAKER --14/2-- |3x-3WAY| --3x14/3-- |3x 3-WAY| ---3x14/2-- LIGHTS
      --------- ---------


      The 3-gang boxes are connected with 3 runs of 14/3 cable.



      My question is: should I splice the neutrals together (and the grounds) at the second 3-gang box (load side)? It seems like it doesn't matter, since they could just as well be going to 3x 1-gang boxes on the load side in which case they would NOT be connected.



      To clarify - I'm not asking if I should connect neutral to ground (I know I shouldn't do that). I'm asking if I should connect all the neutrals together and pigtail off that or just treat each switch independently on the load side.



      Is there a standard way to do it?







      electrical






      share|improve this question









      New contributor



      Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.










      share|improve this question









      New contributor



      Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.








      share|improve this question




      share|improve this question








      edited 8 hours ago







      Harold













      New contributor



      Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.








      asked 8 hours ago









      HaroldHarold

      83 bronze badges




      83 bronze badges




      New contributor



      Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.




      New contributor




      Harold is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.






















          2 Answers
          2






          active

          oldest

          votes


















          1














          If you have an electrical box at the second switch bank location with enough cubic inch volume you should really keep each circuit separate (i.e. not inter tie the neutrals). The primary reason is that you want the current in the hot line (in this case the travellers) and the neutral of each cable to be the same.



          Another good reason for that would be that at some time in the future it may be desirable to bring an alternate power feed to the first switch bank location to feed one lighting circuit separately. You do not want to intermix the neutrals from two separate circuits.






          share|improve this answer























          • Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

            – Harold
            7 hours ago


















          1














          Neutral is not ground



          Neutral is the normal path of current return. Ground is an emergency path, only used if something is seriously wrong (in lieu of sending power through a human, and it helps to get breaker to trip). Because of that, it's OK to spiderweb all grounds to each other. This should never be done with neutral.



          Currents must be equal in each cable or conduit



          Because AC current in wires causes AC magnetism, and the wires' magnetism must cancel each other out. If it doesn't, it will cause eddy current heating, and noise/vibration leading to fatigue, breakage and arcing, both of which can start fires.



          It's a lot to sort out. Mark the wires.



          They sell 5-packs of colored electrical tape for about $5 at the hardware store. Typically blue red yellow green white.



          So you might do something like this in box 1



          enter image description here



          and this in box 2



          enter image description here



          *The neutrals will be a wire from each cable that need be wire-nutted; I simply didn't bother drawing the wire nuts.



          Note how the 2 travelers are color coded the same. That is because there is no need to distinguish travelers from each other.



          I also spiraled the travelers' markings quite some distance, but the switched-hot only the width of the tape.



          Now that looks super clear on the drawing, however in the box, things may be so confusing you need to mark the neutrals too. But you cannot use red, yellow or blue (hot colors) on a neutral wire, or you will inadvertently redefine it as a "hot" wire, which is wrong. White, gray and green don't have that problem. They won't redefine a hot because you're not allowed to redefine a hot to a neutral or ground. White and gray are neutral colors, and green won't redefine a neutral to ground, because that's not allowed either. So brace for an argument with the inspector, but I say using white, gray or green on both hot and neutral does not change the purpose of the wire, therefore is only marking for identification.






          share|improve this answer



























            Your Answer








            StackExchange.ready(function()
            var channelOptions =
            tags: "".split(" "),
            id: "73"
            ;
            initTagRenderer("".split(" "), "".split(" "), channelOptions);

            StackExchange.using("externalEditor", function()
            // Have to fire editor after snippets, if snippets enabled
            if (StackExchange.settings.snippets.snippetsEnabled)
            StackExchange.using("snippets", function()
            createEditor();
            );

            else
            createEditor();

            );

            function createEditor()
            StackExchange.prepareEditor(
            heartbeatType: 'answer',
            autoActivateHeartbeat: false,
            convertImagesToLinks: false,
            noModals: true,
            showLowRepImageUploadWarning: true,
            reputationToPostImages: null,
            bindNavPrevention: true,
            postfix: "",
            imageUploader:
            brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
            contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
            allowUrls: true
            ,
            noCode: true, onDemand: true,
            discardSelector: ".discard-answer"
            ,immediatelyShowMarkdownHelp:true
            );



            );






            Harold is a new contributor. Be nice, and check out our Code of Conduct.









            draft saved

            draft discarded


















            StackExchange.ready(
            function ()
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f169127%2fconnect-neutrals-together-in-3-gang-box-load-side-with-3x-3-way-switches%23new-answer', 'question_page');

            );

            Post as a guest















            Required, but never shown

























            2 Answers
            2






            active

            oldest

            votes








            2 Answers
            2






            active

            oldest

            votes









            active

            oldest

            votes






            active

            oldest

            votes









            1














            If you have an electrical box at the second switch bank location with enough cubic inch volume you should really keep each circuit separate (i.e. not inter tie the neutrals). The primary reason is that you want the current in the hot line (in this case the travellers) and the neutral of each cable to be the same.



            Another good reason for that would be that at some time in the future it may be desirable to bring an alternate power feed to the first switch bank location to feed one lighting circuit separately. You do not want to intermix the neutrals from two separate circuits.






            share|improve this answer























            • Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

              – Harold
              7 hours ago















            1














            If you have an electrical box at the second switch bank location with enough cubic inch volume you should really keep each circuit separate (i.e. not inter tie the neutrals). The primary reason is that you want the current in the hot line (in this case the travellers) and the neutral of each cable to be the same.



            Another good reason for that would be that at some time in the future it may be desirable to bring an alternate power feed to the first switch bank location to feed one lighting circuit separately. You do not want to intermix the neutrals from two separate circuits.






            share|improve this answer























            • Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

              – Harold
              7 hours ago













            1












            1








            1







            If you have an electrical box at the second switch bank location with enough cubic inch volume you should really keep each circuit separate (i.e. not inter tie the neutrals). The primary reason is that you want the current in the hot line (in this case the travellers) and the neutral of each cable to be the same.



            Another good reason for that would be that at some time in the future it may be desirable to bring an alternate power feed to the first switch bank location to feed one lighting circuit separately. You do not want to intermix the neutrals from two separate circuits.






            share|improve this answer













            If you have an electrical box at the second switch bank location with enough cubic inch volume you should really keep each circuit separate (i.e. not inter tie the neutrals). The primary reason is that you want the current in the hot line (in this case the travellers) and the neutral of each cable to be the same.



            Another good reason for that would be that at some time in the future it may be desirable to bring an alternate power feed to the first switch bank location to feed one lighting circuit separately. You do not want to intermix the neutrals from two separate circuits.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered 7 hours ago









            Michael KarasMichael Karas

            46.6k5 gold badges36 silver badges91 bronze badges




            46.6k5 gold badges36 silver badges91 bronze badges












            • Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

              – Harold
              7 hours ago

















            • Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

              – Harold
              7 hours ago
















            Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

            – Harold
            7 hours ago





            Thanks for your rapid response! That's along the lines of what I was thinking. I just wired it and kept everything separate at the second switch box as you suggested.

            – Harold
            7 hours ago













            1














            Neutral is not ground



            Neutral is the normal path of current return. Ground is an emergency path, only used if something is seriously wrong (in lieu of sending power through a human, and it helps to get breaker to trip). Because of that, it's OK to spiderweb all grounds to each other. This should never be done with neutral.



            Currents must be equal in each cable or conduit



            Because AC current in wires causes AC magnetism, and the wires' magnetism must cancel each other out. If it doesn't, it will cause eddy current heating, and noise/vibration leading to fatigue, breakage and arcing, both of which can start fires.



            It's a lot to sort out. Mark the wires.



            They sell 5-packs of colored electrical tape for about $5 at the hardware store. Typically blue red yellow green white.



            So you might do something like this in box 1



            enter image description here



            and this in box 2



            enter image description here



            *The neutrals will be a wire from each cable that need be wire-nutted; I simply didn't bother drawing the wire nuts.



            Note how the 2 travelers are color coded the same. That is because there is no need to distinguish travelers from each other.



            I also spiraled the travelers' markings quite some distance, but the switched-hot only the width of the tape.



            Now that looks super clear on the drawing, however in the box, things may be so confusing you need to mark the neutrals too. But you cannot use red, yellow or blue (hot colors) on a neutral wire, or you will inadvertently redefine it as a "hot" wire, which is wrong. White, gray and green don't have that problem. They won't redefine a hot because you're not allowed to redefine a hot to a neutral or ground. White and gray are neutral colors, and green won't redefine a neutral to ground, because that's not allowed either. So brace for an argument with the inspector, but I say using white, gray or green on both hot and neutral does not change the purpose of the wire, therefore is only marking for identification.






            share|improve this answer





























              1














              Neutral is not ground



              Neutral is the normal path of current return. Ground is an emergency path, only used if something is seriously wrong (in lieu of sending power through a human, and it helps to get breaker to trip). Because of that, it's OK to spiderweb all grounds to each other. This should never be done with neutral.



              Currents must be equal in each cable or conduit



              Because AC current in wires causes AC magnetism, and the wires' magnetism must cancel each other out. If it doesn't, it will cause eddy current heating, and noise/vibration leading to fatigue, breakage and arcing, both of which can start fires.



              It's a lot to sort out. Mark the wires.



              They sell 5-packs of colored electrical tape for about $5 at the hardware store. Typically blue red yellow green white.



              So you might do something like this in box 1



              enter image description here



              and this in box 2



              enter image description here



              *The neutrals will be a wire from each cable that need be wire-nutted; I simply didn't bother drawing the wire nuts.



              Note how the 2 travelers are color coded the same. That is because there is no need to distinguish travelers from each other.



              I also spiraled the travelers' markings quite some distance, but the switched-hot only the width of the tape.



              Now that looks super clear on the drawing, however in the box, things may be so confusing you need to mark the neutrals too. But you cannot use red, yellow or blue (hot colors) on a neutral wire, or you will inadvertently redefine it as a "hot" wire, which is wrong. White, gray and green don't have that problem. They won't redefine a hot because you're not allowed to redefine a hot to a neutral or ground. White and gray are neutral colors, and green won't redefine a neutral to ground, because that's not allowed either. So brace for an argument with the inspector, but I say using white, gray or green on both hot and neutral does not change the purpose of the wire, therefore is only marking for identification.






              share|improve this answer



























                1












                1








                1







                Neutral is not ground



                Neutral is the normal path of current return. Ground is an emergency path, only used if something is seriously wrong (in lieu of sending power through a human, and it helps to get breaker to trip). Because of that, it's OK to spiderweb all grounds to each other. This should never be done with neutral.



                Currents must be equal in each cable or conduit



                Because AC current in wires causes AC magnetism, and the wires' magnetism must cancel each other out. If it doesn't, it will cause eddy current heating, and noise/vibration leading to fatigue, breakage and arcing, both of which can start fires.



                It's a lot to sort out. Mark the wires.



                They sell 5-packs of colored electrical tape for about $5 at the hardware store. Typically blue red yellow green white.



                So you might do something like this in box 1



                enter image description here



                and this in box 2



                enter image description here



                *The neutrals will be a wire from each cable that need be wire-nutted; I simply didn't bother drawing the wire nuts.



                Note how the 2 travelers are color coded the same. That is because there is no need to distinguish travelers from each other.



                I also spiraled the travelers' markings quite some distance, but the switched-hot only the width of the tape.



                Now that looks super clear on the drawing, however in the box, things may be so confusing you need to mark the neutrals too. But you cannot use red, yellow or blue (hot colors) on a neutral wire, or you will inadvertently redefine it as a "hot" wire, which is wrong. White, gray and green don't have that problem. They won't redefine a hot because you're not allowed to redefine a hot to a neutral or ground. White and gray are neutral colors, and green won't redefine a neutral to ground, because that's not allowed either. So brace for an argument with the inspector, but I say using white, gray or green on both hot and neutral does not change the purpose of the wire, therefore is only marking for identification.






                share|improve this answer















                Neutral is not ground



                Neutral is the normal path of current return. Ground is an emergency path, only used if something is seriously wrong (in lieu of sending power through a human, and it helps to get breaker to trip). Because of that, it's OK to spiderweb all grounds to each other. This should never be done with neutral.



                Currents must be equal in each cable or conduit



                Because AC current in wires causes AC magnetism, and the wires' magnetism must cancel each other out. If it doesn't, it will cause eddy current heating, and noise/vibration leading to fatigue, breakage and arcing, both of which can start fires.



                It's a lot to sort out. Mark the wires.



                They sell 5-packs of colored electrical tape for about $5 at the hardware store. Typically blue red yellow green white.



                So you might do something like this in box 1



                enter image description here



                and this in box 2



                enter image description here



                *The neutrals will be a wire from each cable that need be wire-nutted; I simply didn't bother drawing the wire nuts.



                Note how the 2 travelers are color coded the same. That is because there is no need to distinguish travelers from each other.



                I also spiraled the travelers' markings quite some distance, but the switched-hot only the width of the tape.



                Now that looks super clear on the drawing, however in the box, things may be so confusing you need to mark the neutrals too. But you cannot use red, yellow or blue (hot colors) on a neutral wire, or you will inadvertently redefine it as a "hot" wire, which is wrong. White, gray and green don't have that problem. They won't redefine a hot because you're not allowed to redefine a hot to a neutral or ground. White and gray are neutral colors, and green won't redefine a neutral to ground, because that's not allowed either. So brace for an argument with the inspector, but I say using white, gray or green on both hot and neutral does not change the purpose of the wire, therefore is only marking for identification.







                share|improve this answer














                share|improve this answer



                share|improve this answer








                edited 1 hour ago

























                answered 5 hours ago









                HarperHarper

                87.3k5 gold badges63 silver badges177 bronze badges




                87.3k5 gold badges63 silver badges177 bronze badges




















                    Harold is a new contributor. Be nice, and check out our Code of Conduct.









                    draft saved

                    draft discarded


















                    Harold is a new contributor. Be nice, and check out our Code of Conduct.












                    Harold is a new contributor. Be nice, and check out our Code of Conduct.











                    Harold is a new contributor. Be nice, and check out our Code of Conduct.














                    Thanks for contributing an answer to Home Improvement Stack Exchange!


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid


                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.

                    To learn more, see our tips on writing great answers.




                    draft saved


                    draft discarded














                    StackExchange.ready(
                    function ()
                    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f169127%2fconnect-neutrals-together-in-3-gang-box-load-side-with-3x-3-way-switches%23new-answer', 'question_page');

                    );

                    Post as a guest















                    Required, but never shown





















































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown

































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown







                    Popular posts from this blog

                    Canceling a color specificationRandomly assigning color to Graphics3D objects?Default color for Filling in Mathematica 9Coloring specific elements of sets with a prime modified order in an array plotHow to pick a color differing significantly from the colors already in a given color list?Detection of the text colorColor numbers based on their valueCan color schemes for use with ColorData include opacity specification?My dynamic color schemes

                    Invision Community Contents History See also References External links Navigation menuProprietaryinvisioncommunity.comIPS Community ForumsIPS Community Forumsthis blog entry"License Changes, IP.Board 3.4, and the Future""Interview -- Matt Mecham of Ibforums""CEO Invision Power Board, Matt Mecham Is a Liar, Thief!"IPB License Explanation 1.3, 1.3.1, 2.0, and 2.1ArchivedSecurity Fixes, Updates And Enhancements For IPB 1.3.1Archived"New Demo Accounts - Invision Power Services"the original"New Default Skin"the original"Invision Power Board 3.0.0 and Applications Released"the original"Archived copy"the original"Perpetual licenses being done away with""Release Notes - Invision Power Services""Introducing: IPS Community Suite 4!"Invision Community Release Notes

                    199年 目錄 大件事 到箇年出世嗰人 到箇年死嗰人 節慶、風俗習慣 導覽選單